Quality Control and Tests

We design for you, we produce for you.

At Datsan Transformer, every unit we manufacture undergoes rigorous quality control procedures in accordance with the IEC 60076 standard. Our testing protocol is continuously improved to enhance product quality, and our laboratory is equipped with state-of-the-art instruments. Routine tests are performed in-house, while type tests such as short-circuit mechanical withstand are conducted in accredited external laboratories upon customer request.

Routine Tests

Test Description Standard Reference Acceptance Criteria / Method
Winding Resistance Measurement
DC resistance of all windings
IEC 60076-1
Clause 10.1
±2 % maximum deviation between phases; comparison with design values
Insulation Resistance Measurement
Megger test between windings and to earth
IEC 60076-1
Clause 10.2
Minimum 1000 MΩ at 500 VDC; no sudden drop during test
Turns Ratio & Vector Group
Voltage ratio measurement, phase displacement verification
IEC 60076-1
Clause 10.3
Ratio deviation ≤ ±0.5 %; vector group confirmed per nameplate
Short-Circuit Impedance
Zk measurement at rated current
IEC 60076-1
Clause 10.4
Within ±10 % of guaranteed value; phase balance within ±3 %
No-Load Loss & Current
P0 and I0 measurement at rated voltage
IEC 60076-1
Clause 10.5
Losses ≤ guaranteed +15 %; excitation current ≤ guaranteed +30 %
Load Loss
Pk measurement at rated current
IEC 60076-1
Clause 10.6
Losses ≤ guaranteed +15 %; reference temperature corrected
Induced Voltage Test
Overvoltage withstand of insulation
IEC 60076-3
Clause 11.2
No collapse or partial discharge exceedance (if PD measurement applied)
Applied Voltage Test
Separate source AC withstand
IEC 60076-3
Clause 11.1
Withstand specified test voltage for 60 seconds without breakdown

Type Tests

Test Description Standard Reference Acceptance Criteria / Method
Temperature Rise Test
Heat run test at rated load
IEC 60076-2
Clause 7
Top oil temperature rise ≤ 60 K (or 65 K per design); winding ≤ 65 K
Lightning Impulse Test
Full and chopped impulse waves
IEC 60076-4
Clause 7
No flashover or disruptive discharge; voltage waveforms comply with standard
Short-Circuit Mechanical Withstand
Dynamic stability verification
IEC 60076-5
Clause 8
No mechanical damage; impedance variation ≤ 2 % after test; no visible deformation

Special Tests

Test Description Standard Reference Acceptance Criteria / Method
Noise Level Measurement
Sound pressure / power level
IEC 60076-10
Clause 5
Guaranteed LWA value; measured in semi-anechoic or reflective conditions per standard
Zero-Sequence Impedance
For three-phase transformers
IEC 60076-1
Clause 10.9
Measured value reported; used for system protection coordination studies
Partial Discharge Measurement
For Um ≥ 72.5 kV (optional)
IEC 60076-3
Annex A
PD level ≤ 100 pC at 1.5 Um/√3; ≤ 200 pC at 1.3 Um/√3

Our Testing Infrastructure

In-House HV Laboratory

Equipped with modern testing equipment capable of performing all routine tests up to 36 kV class, ensuring full control over quality and delivery timelines.

Accredited Type Tests

Short-circuit withstand, impulse voltage, and temperature rise tests are conducted in collaboration with internationally accredited laboratories (KEMA, CESI, etc.).

Digital Documentation

All test results are digitally recorded and traceable. Comprehensive test reports are provided with every transformer, ensuring full transparency.

Note: All routine tests are performed on 100% of units before shipment. Type tests are conducted according to project specifications and verified by accredited third-party laboratories upon customer request. Special tests are available as optional add-ons per customer requirements.

Transformer Manufacturer

DATSAN Transformer manufactures oil-immersed distribution and power transformers for industrial, utility, and infrastructure projects worldwide. Established in 1992, DATSAN combines over 30 years of engineering experience with modern manufacturing and testing capabilities. Our products are designed in accordance with IEC 60076, ANSI C57 and relevant international standards, with Ecodesign-compliant options available upon request.

Contact us to get information about our products and production.

Transformer Manufacturer

DATSAN Transformer manufactures oil-immersed distribution and power transformers for industrial, utility, and infrastructure projects worldwide.

Established in 1992, DATSAN combines over 30 years of engineering experience with modern manufacturing and testing capabilities. Our products are designed in accordance with IEC 60076, ANSI C57 and relevant international standards, with Ecodesign-compliant options available upon request.